Warning
Lambda workstations are high-performance systems and use a large amount of power. For this reason, Lambda workstations can’t reliably be used with uninterruptible power supplies (UPSs, or battery backups).
If you use a UPS with your workstation, you might experience system instability and trouble booting.
The power requirements for Lambda workstation power supply units (PSUs) are as follows:
Tip
The manufacturer and model of your workstation’s PSU appears on the label on the PSU.Manufacturer | Model | Wattage | Voltage (AC) | Current (A) | Frequency (Hz) | Inlet/Outlet |
---|---|---|---|---|---|---|
Super Flower | SF-1300F14MG V1.0 | 1300 | 100-240 | 15 | 60/50 | C14/C13 |
Super Flower | SF-1600F14HT | 1600 | 115-240 | 17-10 | 60/50 | C20/C19 |
Super Flower | SF-2000F14HP | 2000 | 200-240 | 15 | 50 | C20/C19 |
Power connector inlets and outlets
This is what a C14 inlet looks like:
This is what a C13 outlet looks like:
This is what a C20 inlet looks like:
This is what a C19 outlet looks like:
Power cord plugs and receptacles
Warning
Lambda workstations must be connected to a dedicated power circuit that isn’t shared with other devices. Otherwise, the breaker will trip and disconnect power to the circuit.SF-1300F14MG V1.0 1300W PSU
For customers in North America, the SF-1300F14MG V1.0 1300W PSU power cord has a NEMA 5-15 plug. The plug inserts into NEMA 5-15 and NEMA 5-20 receptacles, which look like this:
On request, a C13-C14 power cord can be substituted for use with power distribution units (PDUs) commonly found in data centers.
SF-1600F14HT 1600W PSU
For customers in North America, the SF-1600F14HT 1600W PSU power cord uses a NEMA 5-20 plug. The plug inserts into a NEMA 5-20 receptacle, which looks like the receptacle on the right in the picture, below.
On request, a C19-C20 power cord can be substituted for use with power distribution units (PDUs) commonly found in data centers.
SF-2000F14HP 2000W PSU
For customers in North America, the SF-2000F14HP 2000W PSU power cord uses NEMA 6-20 or NEMA 6-15 connectors, which look like the ones in the third row in the picture, below.
On request, a C19-C20 power cord can be substituted for use with power distribution units (PDUs) commonly found in data centers.